www.DaikinApplied.com 29 OM 1085-6 • MICROTECH III CONTROLLER

Model Number
Number of
Compressors
1 Speed Fan 2 Speed Fan 3 Speed Fan HGR Dehumid
Supplemental
Electric Heat
Boilerless
Electric Heat
1
1
Single X
2 Single X X
3 Single X X
4 Single X X
5 Single X X X
6 Single X X X
7 Single X
8 Single X X
9 Single X X
10 Single X X
11 Single X X X
12 Single X X X
13 Single X X
14 Single X X
15 Single X X X
16 Single X X X
17 Dual X
18 Dual X X
1

2
An “X” means that option is available for the corresponding WSHP model.
SmartSource Single and Two Stage Compressor (Series2) and SmartSource
Compact

SmartSource Compact
Unit Controller Option Hardware Jumpers Setting Description
Normal / Test Mode JP1
JP1 = Open Normal Operation
JP1 = Shorted Service / Test Mode
Fan Operation JP2
JP2 = Open Continuous Fan Operation (ON)
JP2 = Shorted Cycling Fan Operation (AUTO)
Loop Fluid JP3
JP3 = Open Water Loop Fluid
JP3 = Shorted Glycol Loop Fluid
Freeze Fault Protection JP4
JP4 = Open LWT Freeze Fault Protection is Disabled
JP4 = Shorted LWT Freeze Fault Protection is Enabled
Room Sensor Setpoint Adjust Range JP5
JP5 = Open Short Range: -5 to +5 ºF (-2.78 to +2.78 ºC)
JP5 = Shorted Long Range: 55 to 95 ºF (12.78 to 35 ºC)
Thermostat / Room Sensor JP6
JP6 = Open Thermostat Control
JP6 = Shorted Room Sensor Control
Compressor Heating Source JP7
JP7 = Open Allow Compressor Heating Mode Operation
JP7 = Shorted Disable Compressor Heating Mode Operation
I/O Expansion Module JP8
JP8 = Open I/O Expansion Module is Not Present
JP8 = Shorted I/O Expansion Module is Required