IM 1285-4 • MICROTECH III 36 www.DaikinApplied.com

Figure 30 continued: ATV 212 (MD2) Drive Parameters
PART NUMBER REV
PART DESCRIPTION
170632000
B Rooftop - MT3 SAF (set 321) PARAMETERS
Drive Voltage HP Application
ATV21 ALL ALL
SAF/RAF, RT/SC
Code Function Description Unit Min. Value Max. Value
Default
Value
New Value
Logical
Address
F207
Frequency setting mode selection 2
1152
207
F210
VIB input point 1 setting
1% 0 100 0
210
F211
VIB input point 1 frequency
0.01Hz 0,00 200,00 0
211
F212
VIB input point 2 setting
1% 0 100 100
212
F213
VIB input point 2 frequency
0.01Hz 0,00 200,00 50
213
F240
Starting frequency setting
0.01Hz 0,50 10,00 0.5
240
F241
Operation starting frequency
0.01Hz 0,00 80,00 0
241
F242
Operation starting frequency hysteresis
0.01Hz 0,00 80,00 0
242
F250
DC braking starting frequency
0.01Hz 0,00 80,00 0
250
F251
DC braking current
1% 0 100 50
251
F252
DC braking time
0.1sec 0,0 20,0 1
252
F256
Time limit for lower-limit frequency operation
0.1sec 0,0 600,0 0
256
F264
Input from external contacts-UP response time
0.1sec 0,0 10,0 0.1
264
F265
Input from external contacts-UP frequency step width
0.01Hz 0,00 80,00 0.1
265
F266
Input from external contacts-DOWN response time
0.1sec 0,0 10,0 0.1
266
F267
Input from external contacts-DOWN freq step width
0.01Hz 0,00 80,00 0.1
267
F268
Initial value of UP/DOWN frequency
0.01Hz 0,00 60,00 0 20
268
F269
Saving of changed value of UP/DOWN frequency
1011
269
F270
Jump frequency 1
0.01Hz 0,00 80,00 0
270
F271
Jump width 1
0.01Hz 0,00 30,00 0
271
F272
Jump frequency 2
0.01Hz 0,00 80,00 0
272
F273
Jump width 2
0.01Hz 0,00 30,00 0
273
F274
Jump frequency 3
0.01Hz 0,00 80,00 0
274
F275
Jump width 3
0.01Hz 0,00 30,00 0
275
F294
Preset-speed operation frequency 15
0.01Hz 0,00 60,00 50
294
F295
Selection of bumpless
1011
295
F300
PWM carrier frequency
0.1kHz 6,0 16,0
300
F301
Auto-restart control selection
1043
301
F302
Regeneration power ride-through control (Deceleration stop)
1020
302
F303
Retry selection (number of times)
1 0 10 3 5
303
F305
Over-voltage limit operation (Slowdown stop mode selection)
1032
305
F307
Supply voltage correction (limitation of output voltage)
1033
307
F311
Reverse-run prohibition
1021
311
F312
Random mode
1010
312
F316
Carrier frequency control mode selection
1031
316
F320
Drooping gain
1% 0 100 0
320
F323
Drooping insensitive torque band
1% 0 100 10
323
F359
PID control waiting time
1sec 0 2400 0
359
F360
PID control
1020
360
F362
Proportional gain
0.01 0,01 100,00 0.3
362
F363
Integral gain
0.01 0,01 100,00 0.2
363
F366
Differential gain
0.01 0,00 2,55 0
366
F400
Auto-tuning
1020
400
F401
Slip frequency gain
1% 0 150 50
401
F402
Motor constant #1 (primary resistance)
0.10% 0,0 30,0
402
F415
Motor rated current
0.1A 0,1 200,0
415
F416
Motor no-load current
1% 10 100
416
F417
Motor rated speed
1min-1 100 15000
417
F418
Speed control response coefficient
1 1 150 40
418
F419
Speed control stability coefficient
1 1 100 20
419
F470
VIA bias
1 0 255 128
470
ATV21 MT3 SAF PAGE 2