3 | Components
Service manual
142
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
INFORMATION
Winding resistance values above are given for reference. You should NOT be reading
a value in or a short‑circuit. Make sure that the propeller fan blade does NOT
rotate, as this could affect resistance measurements.
9 Set the Megger voltage to 500VDC or 1000VDC.
10 Measure the insulation resistance for the motor terminals. Measurements
between each phase and fan motor body (e.g. axle) MUST be >1000MΩ.
Are the measured resistance values
correct?
Action
Yes Perform a check of the main PCB, see
"Checking procedures"[4123].
No Replace the DC fan motor, see "Repair
procedures"[4142].
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the propeller fan blade assembly
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see "3.14Plate work"[4151].
2 Remove the nut that fixes the propeller fan blade assembly.