EasyManuals Logo

Daikin R24NUV2S User Manual

Daikin R24NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
Si20-701_B Troubleshooting by Remote Controller
96
3.8
A6
Fan Motor (M1F) Lock,
Overload
Remote Controller Display
A6
Applicable Models
FMCQ, FMDQ
Method of Error Detection
Detection by failure of signal for detecting number of
turns to come from the fan motor
Error Decision Conditions
When number of turns can not be detected even when
output voltage to the fan is maximum
Supposed Causes
îš„ Fan motor lock
îš„ Disconnected or defective wiring between fan motor
and PCB

Table of Contents

Other manuals for Daikin R24NUV2S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin R24NUV2S and is the answer not in the manual?

Daikin R24NUV2S Specifications

General IconGeneral
BrandDaikin
ModelR24NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals