EasyManuals Logo

Daikin R24NUV2S User Manual

Daikin R24NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #304 background imageLoading...
Page #304 background image
Troubleshooting by Remote Controller Si20-701_B
297
3.67
L8
Inverter Current
Abnormality
Remote Controller Display
L8
Applicable Models
CMSQ
Method of Error Detection
The error is detected by current flowing in the power
transistor.
Error Decision Conditions
When overload in the compressor is detected. (Inverter
secondary current 16.1A)
Supposed Causes
îš„ Compressor overload
îš„ Compressor coil disconnected
îš„ Defective inverter PCB
îš„ Defective compressor

Table of Contents

Other manuals for Daikin R24NUV2S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin R24NUV2S and is the answer not in the manual?

Daikin R24NUV2S Specifications

General IconGeneral
BrandDaikin
ModelR24NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals