EasyManuals Logo

Daikin R24NUV2S User Manual

Daikin R24NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #277 background imageLoading...
Page #277 background image
Si20-701_B Troubleshooting by Remote Controller
270
3.60
L4
Radiation Fin Temperature
Rise
Remote Controller Display
L4
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZQG, RZR-KU/HU
Method of Error Detection
Radiation fin temperature is detected by the radiation fin
thermistor.
Error Decision Conditions
When the temperature of the inverter radiation fin rises
abnormally due to defective heat dissipation.
Supposed Causes
îš„ Defective radiation fin thermistor
îš„ High outdoor air temperature
îš„ Blocked suction opening
îš„ Dirty radiation fin
îš„ Defective outdoor inverter PCB
îš„ Activation of fin thermal switch (For RZQ-K, RZQ(S)-
B/C, RZQG, RZR-KU/HU)
îš„ Insufficient cooling of inverter radiation fin (For RZQ-K,
RZQ(S)-B/C, RZQG, RZR-KU/HU)
îš„ Defective propeller fan (For RZR-KUV2S)

Table of Contents

Other manuals for Daikin R24NUV2S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin R24NUV2S and is the answer not in the manual?

Daikin R24NUV2S Specifications

General IconGeneral
BrandDaikin
ModelR24NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals