EasyManuals Logo

Daikin R24NUV2S User Manual

Daikin R24NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #351 background imageLoading...
Page #351 background image
Si20-701_B Troubleshooting by Remote Controller
344
Troubleshooting
Note:
∗ Capacity setting adaptor is not connected at factory.
(Capacity is written in E
2
PROM.) Capacity setting
adaptor is required only when the PCB was replaced
with a spare PCB.
Has the
PCB been replaced?
NO
Is the type
of PCB correct?
Replace with a
correct PCB.
Is the
correct
capacity setting
adaptor connected to the
outdoor unit PCB?
(∗)
NO
NO
Mount the correct
capacity setting
adaptor correctly.
Reset, and then
restart.
YES
YES
YES
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.

Table of Contents

Other manuals for Daikin R24NUV2S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin R24NUV2S and is the answer not in the manual?

Daikin R24NUV2S Specifications

General IconGeneral
BrandDaikin
ModelR24NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals