Daikin R30NUV1 - 3.42 H3 High Pressure Switch System Abnormality

Daikin R30NUV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
221
Troubleshooting
Refer to P.464.
NO
Is the stop
valve open?
NO
YES
Open the stop
valve.
Check for the installation
conditions.
CHECK 4
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
High pressure
is too high.
YES
Correct the high
pressure.
• In cooling
operation: Dirty
outdoor unit
heat exchanger
• In heating
operation: Dirty
indoor unit heat
exchanger
• Excessive
charging of
refrigerant
Replace the
outdoor unit
PCB.
CHECK 4