EasyManua.ls Logo

Daikin R30NUV1 - After Unit Shuts Down, It Cannot be Restarted for a While

Daikin R30NUV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si20-701_B Symptom-based Troubleshooting
38
2.5 After Unit Shuts Down, It
cannot be Restarted for a
While
Applicable Model
All models of SkyAir series
Supposed Causes
Overcurrent relay (for compressor)
Overcurrent relay may act due to the following
reasons
Lower voltage of power supply
Excess level of high pressure
Insufficient size of power cable
Defective compressor
Compressor protection thermostat
Compressor protection thermostat may act due to the
following reasons
Internal leakage of four way valve (There is no
difference between suction air temperature and
discharge pipe temperature)
Insufficient compression of compressor
Incorrect refrigerant
Defective electronic expansion valve
Insufficient circulation of refrigerant