Troubleshooting Si10-417
164 Service Diagnosis
5.4.13 Main Circuit Electrolytic Capacitor Check
Check
No.14
Checking the main circuit electrolytic capacitor
z
Never touch any live parts for at least 10 minutes after
turning off the circuit breaker.
z
If unavoidably necessary to touch a live part, make
sure there is no DC voltage using the tester.
z
Check the continuity with the tester. Reverse the pins
and make sure there is continuity.
Si10-417.fm Page 164 Wednesday, September 22, 2004 6:38 PM