Si10-417 Troubleshooting
Service Diagnosis 167
5.4.15 Hall IC Check
Check
No.16
1. Check the connector connection.
2. With the power ON, operation OFF, and the connector
connected, check the following.
Output voltage of about 5 V between pins 1 and 3.
Generation of 3 pulses between pins 2 and 3 when
the fan motor is operating.
Failure of (1)
Æ
faulty PCB
Æ
Replace the PCB.
Failure of (2)
Æ
faulty hall IC
Æ
Replace the fan motor.
Both (1) and (2) result
Æ
Replace the PCB.