Si20-701_B Troubleshooting by Remote Controller
80
Troubleshooting
YES
NO
NO
External
protection
device is connected
to terminals T1 and T2
of the indoor unit
terminal
block.
Actuation of
external
protection device.
Change the
second code No.
to "01" or "02" .
Replace the
indoor unit PCB.
YES
External
ON/OFF
input (mode No.
12, first code No.
1) has been set to
external protection
device input (second
code No. 03) by
remote
controller.
Check the setting state of
the ON/OFF input from
outside by remote
controller.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.