TECHNICAL MANUAL
Inverter Single Split Air Conditioner
Wall Mounted A Series
FTXS-A Series
— Heatpump [50Hz] —
R410A
TM-5WMZR-SI-ARA1

Questions and Answers

  • T
    Terri NguyenAug 15, 2025
    What to do if Daikin RXN60CXV1G Air Conditioner shows A5?
    • G
      Gabriella FranklinAug 15, 2025
      If your Daikin Air Conditioner is showing the A5 error, here are some things you can check: 1. Make sure the air passage isn't blocked. 2. Inspect the intake air filter. 3. Check for dust on the indoor coil. 4. Examine the wiring and piping. 5. Inspect the EXV. 6. Check the indoor coil and room sensor resistance values. 7. Verify the refrigerant level.
  • M
    Michael JamesAug 18, 2025
    What to do if Daikin Air Conditioner shows U4?
    • J
      John CoxAug 18, 2025
      If your Daikin Air Conditioner displays the U4 error code, you can try the following troubleshooting steps: 1. Check the connection wires between the indoor and outdoor units. 2. Check the voltage of the signal terminal. 3. Manually rotate the indoor fan to check for obstructions. 4. Check the power supply waveform.
  • W
    William WilliamsAug 21, 2025
    How to troubleshoot E5 error on Daikin RXN60CXV1G Air Conditioner?
    • C
      Cindy PayneAug 21, 2025
      To troubleshoot an E5 error on your Daikin Air Conditioner: 1. Check the connection on the discharge pipe sensor. 2. Check the discharge pipe sensor resistance value. 3. Inspect the EXV. 4. Check the refrigerant line for blockages or shortages.
  • D
    David ConnerAug 25, 2025
    How to troubleshoot Daikin RXN60CXV1G Air Conditioner error H6?
    • B
      Brian MontgomeryAug 26, 2025
      To troubleshoot an H6 error on your Daikin Air Conditioner, you can try these steps: 1. Check for a short circuit. 2. Check the electrolytic capacitor voltage. 3. Check the compressor harness wire. 4. Check with inverter checker.
  • M
    Martha MillerAug 28, 2025
    How to troubleshoot Daikin RXN60CXV1G Air Conditioner error F6?
    • J
      Jesse SchultzAug 28, 2025
      To troubleshoot an F6 error on your Daikin Air Conditioner, you can try: 1. Checking the installation space. 2. Checking the outdoor fan. 3. Checking the EXV. 4. Checking the coil sensor.
  • M
    Michelle FlynnAug 31, 2025
    What to do if Daikin RXN60CXV1G shows error A1?
    • S
      Suzanne RodriguezAug 31, 2025
      If your Daikin Air Conditioner is displaying the A1 error, you can: 1. Check the connector connection. 2. Replace the indoor PCB.
  • T
    Todd WalkerSep 4, 2025
    How to fix E1 error on Daikin RXN60CXV1G Air Conditioner?
    • C
      Chloe ContrerasSep 4, 2025
      To address an E1 error on your Daikin Air Conditioner: 1. Restart the system. 2. Replace the outdoor PCB. 3. Ensure the unit is properly grounded. 4. Check the power supply waveform.
  • S
    Steven GrimesSep 7, 2025
    What to do if Daikin Air Conditioner shows H0 error?
    • A
      April DunnSep 7, 2025
      If your Daikin Air Conditioner is showing the H0 error, you should: 1. Check the reactor connection. 2. Check the compressor connection. 3. Measure the resistance value between the reactor terminals. 4. Measure the resistance value between the compressor terminals.
  • V
    vmooreSep 10, 2025
    What to do if Daikin RXN60CXV1G shows J3 error?
    • A
      andrew23Sep 10, 2025
      If your Daikin Air Conditioner is showing the J3 error, you should: 1. Check the sensor connection. 2. Check the sensor resistance value. 3. Check the indoor coil sensor resistance value.

Summary

Application Information

Cooling Operating Range

Shows operating temperature limits for cooling.

Heating Operating Range

Shows operating temperature limits for heating.

Installation Guideline

Installation Diagram

Provides a visual guide for installing the unit.

Outdoor Clearance

RXN25;35 F Clearance

Specifies clearance requirements for outdoor units.

RXN50;60 C Clearance

Specifies clearance requirements for outdoor units.

Cable Size and Piping

Refrigerant Piping Guidelines

Covers piping length and elevation.

Performance Data

Wiring Diagram

Indoor Unit Wiring Diagram

Electrical wiring diagram for indoor units.

Outdoor Unit Wiring Diagram

Electrical wiring diagram for outdoor units.

Service & Maintenance

Maintenance Procedures by Component

Details maintenance tasks for various components.

Service & Maintenance

Troubleshooting

Error Code Diagnosis Steps

Steps to initiate error code diagnosis.

Troubleshooting Guidelines

Error Codes U0-E5

Lists error codes and their actions.

Error Codes E6-J3

Lists error codes and their actions.

Error Codes J6-P4

Lists error codes and their actions.

Daikin RXN60CXV1G Specifications

General IconGeneral
CategoryAir Conditioner
ModelRXN60CXV1G
ManufacturerDaikin
TypeSplit System
Cooling Capacity6.0 kW
RefrigerantR32
Power Supply220-240V, 50Hz