Main Functions SiEN04-306D
48 Function and Control
1.6 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Heating
B
A
OFF
OFF
ON
ON
C
Room temperature - setpoint
(R4668)
Cooling : -0.5°C
Dry : -0.5°C
Cooling : -2.0°C
Dry : -2.5~-2.0°C
B
A
OFF
OFF
ON
ON
C
1.5°C
Room temperature - setpoint
0°C
(R4669)