5 Installation
Installation manual
18
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695306-1 – 2022.05
c
a
d
e
1~ 50 Hz
220-240 V
3N~ 50 Hz
380-415 V
V1 Y1
L1 L2 L3
L1 L2 L3
N
b
b
a
a
a
I, II, III, IV Pair, twin, triple, double twin
M, S Master, slave
a Interconnection cables
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e User interface
INFORMATION
Some indoor units may need a separate power supply in
order to guarantee maximum capacity. See the installation
manual of the indoor unit.
V1
a
b
d
c
Y1
a
b
d
c
a Interconnection cable
b Power supply cable
c Earth
d Cable tie
3 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration above.
4 Choose a knockout hole and remove the knockout hole by
tapping on the attachment points with a flat head screwdriver
and a hammer.
5 Route the wiring through the frame and connect the wiring to
the frame at the knockout hole.
Routing through
the frame
Choose one of the 3 possibilities:
a
a
a
2
3
1
a Power supply cable
Note: Route the interconnection cable
together with the refrigerant piping. See
"5.6.1To finish the outdoor unit
installation"[419].
Connecting to the
frame
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
a b
A B
c d e
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
NOTICE
Precautions when making knockout holes:
Avoid damaging the casing and underlying piping.
After making the knockout holes, we recommend to
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
6 Reattach the service cover.
7 Connect an earth leakage circuit breaker and fuse to the power
supply line.