EasyManua.ls Logo

Daikin Sky Air Alpha RZAG71N2Y1B - To Connect the Refrigerant Piping to the Outdoor Unit

Daikin Sky Air Alpha RZAG71N2Y1B
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 | Installation
Installer reference guide
44
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
7.4.8 To connect the refrigerant piping to the outdoor unit
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical damage.
1 Do the following:
Remove the service cover (a) with screw (b).
Remove the piping intake plate (c) with screws (d).
a
c
b
d d
2 Choose a piping route (a, b, c or d).
a
d
b
c
a Front
b Side
c Rear
d Bottom
INFORMATION
b b bb
a
a
Remove the knockout hole (a) in the bottom plate or cover plate by tapping on
the attachment points with a flat head screwdriver and a hammer.
Optionally, cut out the slits (b) with a metal saw.

Table of Contents

Related product manuals