EasyManua.ls Logo

Daikin Skyair FHC35K - Removal of 4-Way Valve and Coil

Daikin Skyair FHC35K
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si-71A For R(Y)71K
Removal Procedure 187
6.6 Removal of 4-Way Valve and Coil
Procedure
Waring Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
Make sure the refrigerant is
completely empty.
1 Remove the external casing,
etc., and electrical parts
according to their removal
procedures.
2 Remove the 4-way valve.
3 Heart the brazed parts of the
4-way valve, and remove the
assembly from the piping
side by drawing out with a
pair of pliers, etc.
Note:
Apply the flame while cooling with a
leak cloth so that the temperature of
the main body doesn’t rise above
120 ºC.
Note:
When installing, first braze weld the 4-
way valve and attached piping, then
install the valve.
Be sure to check the position angle of
the piping when brazing.

Table of Contents