EasyManua.ls Logo

Daikin Trailblazer AGZ226-241E - Page 6

Daikin Trailblazer AGZ226-241E
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 2 of 2
6. Change parameter 6-23 to match the high end of current signal from the sensor (eg: if your sensor
provides a 4-20mA signal, enter 20). Go to step 7.
7. Change parameter 20-00 (default value is option 105 Sensorless Pressure”) to option 2 Analog input
54” to make drive look at sensor reading for feedback value
8. Change parameter 20-12 to the unit that matches your sensor measurement units (eg: if you have a
pressure sensor, it will be in units of pressure like psi)
9. Change parameter 20-13 to the value that matches the bottom end of your sensor measurement scale
(eg: if your pressure sensor measures from 2-100psi, you enter a value of 2)
10. Change parameter 20-14 to the value that matches the high end of your sensor measurement scale
(eg: if your pressure sensor measures from 2-100psi, you enter a value of 100)
11. Set parameter 20-21 the setpoint you want the pump to maintain
12. Change parameter 22-80 (default value is 1 “Enabled”) to option 0 “Disabled”
13. Put the VFD into AUTO mode it will now display the sensor reading in the center of the screen and
the target setpoint on the top left of the screen. It will ramp up / down to meet the setpoint based on the
sensor reading.
Section 3 EXTERNAL CONTROLLER (BAS) Startup Procedure:
NOTE: Speed signal wire must be connected to analog input terminal 53
1. Open up and bleed pump seal flush line to verify no air has travelled into seal / seal lines
2. Change parameter 0-20 to option 1602 “Reference %” to show the percent speed signal on top left
corner
3. Change parameter 1-00 to option 0 “Open Loop” (drive will ‘listen’ for external speed reference)
4. Change parameter 3-02 to “0” (this is the minimum speed signal)
5. Change parameter 3-03 to “60” (this is the maximum speed signal)
6. Change parameter 3-15 to option 1 “Analog Input 53”
7. Put the VFD into AUTO mode the VFD will now ramp up / down based on the analog speed signal it
receives on terminal 53. You can check what the drive is seeing on the input by going to parameter 16-62.

Related product manuals