20 | P a g e
Status/Settings
No.
Menu
Property
Unit
Description
1.
Unit Status
R
-
View the current operation status of the
unit
2.
Next Crkt On
R
-
View the next circuit to be started
3.
Next Crkt Off
R
-
View the next circuit to be stopped
4.
Chiller Enable
R
-
Used to enable the unit
Enable: Allow the unit to be started
Disable: Prohibit the unit to be started
5.
Control Source
R
-
View and set the control source of the
unit. The options are as follows:
Local: The unit is controlled by control
panel
Network: The unit is controlled by local
panel and network
6.
Netwrk En SP
R
-
View the status of BAS switch
7.
Netwrk Mode SP
R
-
View the mode setting of BAS
8.
Netwrk Cool SP
R
°C
View the BAS cooling setpoint
9.
Netwrk Ice SP
R
°C
View the BAS ice storage setpo int
10.
Netwrk Cap Lim
R
%
View the network capacity limitation of
the unit
11.
Stg Up Dly Rem
R
s
View remaining time before next
compressor start
12.
Stg Dn Dly Rem
R
s
View remaining time before next
compressor stop
13.
Ice Cycle Rem
R
min
View the remaining time of an ice
storage cycle
14.
Evap Pmp 1Hrs
R
Hour
View the running time of pump 1
15.
Evap Pmp 2Hrs
R
Hour
View the running time of pump 2
16.
Remote Srv En
R/W
-
Reserved