24 | P a g e
Power Conservation
No.
Menu
Property
Uni
t
Description
1
Unit Capacity
R
%
View the current capacity of the unit
2
Unit Current
R
A
View the working current of the unit
3
Demand Lim En
R
--
View whether demand capacity limitation
is enabled
4
Demand Limit
R/W
%
View or set demand capacity limitation of
the unit
5
Current @20mA
R
A
View the current for 20mA
6
Current Limit
R
A
View the current limitation of the unit
7
Setpoint
Reset
R/W
--
Adjust the evaporator leaving water
temperature setpoint:
None: No adjust to the setpoint
4-20mA: Adjust the settings based on
external current signal
Return: Adjust the settings based on
evaporator water temperature
Oat: Adjust the settings based on ambient
temperature
8
Max Reset
R/W
°C
View or set the maximum reset
9
Start Reset DT
R/W
°C
View or set the temperature difference
between evaporator entering and
leaving water using “Return” to adjust
the evaporator leaving water
temperature setpoint
No.
Menu
Property
Unit
Description
13
QM Start Hr
R/W
--
View or set the hour when the quiet mode
takes effect
14
QM Start Min
R/W
--
View or set the minute when the quiet
mode takes effect
15
QM End Hr
R/W
--
View or set the hour when the quiet mode
finishes
16
QM End Min
R/W
--
View or set the minute when the quiet
mode finishes
17
QM Cond Offset
R/W
°C
View or set the condenser temperature
difference for the quiet mode