Loading...
Page | 35
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
Holiday5
0mon 0day
Holiday6
0mon 0day
Holiday7
0mon 0day
Holiday8
0mon 0day
Holiday9
0mon 0day
Holiday10
0mon 0day
Quiet Mode
Disable
Disable
Enable
--
U
U
QM Start Hr
21
18
23
hour
U
U
QM Start Min
0
0
59
min
U
U
QM End Hr
6
5
9
hour
U
U
QM End Min
0
0
59
min
U
U
QM Cond Offset
5.0
0.0
14.0
dK
U
U
3.5.Power Conservation
Demand Lim En
Disable
Disable
Enable
--
U
U
Current @ 20mA
800.0
0.0
2000.0
A
U
S
Current Limit
800.0
0.0
2000.0
A
U
S
Setpoint Reset
None
--
--
U
U
Max Reset
5.0
0.0
10.0
dK
U
U
Start Reset DT
5.0
0.0
10.0
dK
U
U
Max Reset OAT
15.5
10.0
29.4
U
U
Strt Reset OAT
23.8
10.0
29.4
U
U
Softload En
Disable
Disable
Enable
--
U
U
Softload Ramp
20
1
60
min
U
U
Starting Cap
40.0
20.0
100.0
%
U
U
3.6.Configuration
Apply Changes
No
No
Yes
--
S
S
M/A Setting
Single
Single
Master
Auxiliary
--
S
S
Number Of Ckts
1
1
2
--
S
M
Slide Pos Sens
No
No
Yes
--
S
M
Unit Model
ST3
ST3
SP3
--
S
S
Display Units
Metric
Metric
English
--
S
S
Comm Module 1
None
Modbud
AWM
MSTP
LON
IP
None
--
S
S
Comm Module 2
None
Comm Module 3
None
Curr Prot Type
Switch
Switch
Current
--
S
S
3.7.Ctrlr IP Setup
Apply Changes
No
No
Yes
--
U
U
DHCP
On
No
Yes
--
U
U
Gvn IP
192.168.1.42
0.0.0.0
255.255.255.25
5
--
U
U
Gvn Msk
255.255.255.0
--
U
U
Gvn Gwy
192.168.1.1
--
U
U