36 | P a g e
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
3.8.Design Conditions
Evap Dsn EWT
0.0
-64.0
64.0
U
M
Evap Dsn LWT
Evap Dsn Flow
0.0
0.0
600000
l/h
S
M
Evap Dsn Approach
Cir#1
0.0
-64.0
64.0
dK
S
M
Evap Dsn Approach
Cir#2
0.0
Cond Dsn Approach
Cir#1
0.0
Cond Dsn Approach
Cir#2
0.0
Design FL Eff
0.0
-64.0
64.0
%
M
M
Design IPLV
0.0
-64.0
64.0
--
M
M
Rated Cap
0
0
10000
Tons
U
M
3.9.Alarm Limits
Low Press Hold
C:165.0
155
310.0
kPa
S
M
0.0
310.0
Low Press Unld
C:150.0
140.0
310.0
kPa
S
M
0.0
310.0
Hi Oil Pr Dly
30
10
180
s
S
S
Hi Oil Pr Diff
250.0
0.0
415.0
kPa
S
S
Hi Disch Temp
110.0
65.0
110.0
S
S
Hi Cond Pr Dly
5
0
30
s
S
M
Lo Pr Ratio Dly
90
30
300
s
S
M
Low Disch SH
12
10.0
15.0
dK
S
S
Low DSH SSH Set
1.0
1.0
8.5
dK
S
S
Cool OAT Lockout
4.0
-23.0
15.0
S
M
Heat OAT Lockout
-11.0
-23.0
15.0
S
M
Strt Time Lim
60
20.0
180.0
s
S
S
Evap Water Frz
2.2
2.0
6.0
S
M
Evap Flw Proof
15
5
15
s
S
S
Evp Rec Timeout
3
1
10
min
S
S
Heat HP Al Offset
0.0
0.0
-9.0
dK
S
M
Sld Pos Min Al1
1.0
0.1
1.0
mA
S
M
Sld Pos Min Al2
1.0
0.1
1.0
mA
S
M
HR Water Frz
3.0
2.0
6.0
S
S
Comp Over Ld Dly
15
1
30
s
S
M
Min Curr Sp
15.0
0.0
30.0
A
S
S
3.10.Calibrate Sensors
Evp LWT Offset
0.0
-2.8
2.8
dK
S
S
Evp EWT Offset
0.0
OAT Offset
0.0
HR LWT1 Offset
0.0
HR LWT2 Offset
0.0
3.11.Menu Password
Pwd Disable
Off
Off
On
--
U
S