Page | 37
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
4.View/Set Circuit #1/#2
4.1.Status/Settings
Circuit Mode
Enable
Disable
Enable
--
S
S
Service Pumpdn
Off
Off
On
--
S
S
Defrost Time Clr
Clr Dfrst Tmr
No
No
Yes
--
S
S
Unload Curr Limit
148.0
50.0
Corresponding
to Comp Size
A
S
S
4.2.Comp 1 / 2
Run Hours
--
0
999999
hour
U
M
No. Of Starts
--
0
65535
--
U
M
Clear Cycle Time
Off
Off
On
--
S
S
Cap Control
Auto
Auto
Manual
--
S
S
Manual Cap
0.0
0.0
100.0
%
S
S
50/60CompLoad2DelT
4
4
20
s
M
M
4.3.Condenser
Cond Min Temp
36.0
26.0
43.0
S
M
Cond Max Temp
43.0
32.0
50.0
S
M
Stg On Db 0
C:4.0
1.0
10.0
dK
S
M
Stg On Db 1
C:5.0
Stg On Db 2
C:5.5
Stg On Db 3
C:6.0
Stg On Db 4
C:6.5
Stg On Db 5-13
C:6.5
Stg Off Db 2
C:10.0
1.0
13.0
dK
S
M
Stg Off Db 3
C:8.0
Stg Off Db 4
C:5.5
Stg Off Db 5
C:4.0
Stg Off Db 6-14
C:4.0
4.4.EXV
EXV Ctrl Mode
Auto
Auto
Manual
--
S
S
EXV Position
0.0
0.0
100.0
%
S
S
4.5.Configuration
Apply Changes
No
No
Yes
--
S
S
Mtr Tmp Sensor
Disable
Disable
Enable
--
S
M
Fan VFD Enable
Disable
Disable
Enable
--
S
M
Number Of Fans
10
5
14
--
S
M