Page | 71
Alarm
C#Cmp# Off Compressor Motor Hi
Temp Normal
Code:
C#Cmp#OffMotorTempHiOffNormal
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Motor protection input = closed
Solution
Check refrigerant charge (overcharged)
Alarm
Motor protection input = Open?
No
Yes
Confirm Time
= 2 sec?
No
Yes