Alarm
C#Cmp# Off Compressor Overload
Normal
Code:
C#Cmp#CompOverloadOffNormal
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Motor overload input = closed
Solution
Check ammeter setting as per recommended in wiring diagram
Check ammeter wiring and condition
Check CT condition and wiring
Alarm
Motor Overload input = Open?
No
Yes
Confirm Time
= 2 sec?
No
Yes