Loading...
10 | P a g e
Chiller Physical Data
UAA
105
125
150
175
204
220
245
291
348
380
400
450
Nominal cooling capacity
kW
370
449
586
663
717
802
898
1035
1172
1326
1434
1604
USRT
105
128
167
189
204
228
255
294
333
377
408
456
×10
4
kcal/h
32
39
50
57
62
69
77
89
101
114
123
138
Total power input for cooling
kW
115.5
138.5
178.7
201.3
216.1
242.6
277.0
317.2
357.4
402.6
432.2
485.2
Power supply
380-400V/3N~/50Hz
Maximum running current
A
321
349
431
505
540
637
698
780
861
1011
1080
1275
Starting current
A
473
480
708
715
715
740
829
1057
1139
1221
1255
1377
Energy regulation range
10%~100%
5%~100%
Refrigerant
Type
R134a
No. of Sys.
1
2
Control
Electronic Expansion Valve
Compressor
Type
Semi-hermetic Single-screw
Qty. X Model
HSS
1x3221b
1×3222b
1x4224a
1x4225a
1x4226a
1x4227a
2x3222b
1x3222b
1x4224a
2×4224a
2×4225a
2×4226a
2x4227a
Cooling motor
power
kW
103.5
122.5
158.7
177.3
192.1
214.6
245.0
281.2
317.4
354.6
384.2
429.2
Oil type
FVC68D
Oil charge
L
22
22
28
28
28
28
44
50
56
56
56
56
Condenser
Type
Crossed Fin and Tube
Fan
Type
High-efficient Spiral Axial
Qty.
n
6
8
10
12
12
14
16
18
20
24
24
28
Total air flow
x10
4
m
3
/h
10.8
14.4
18.0
21.6
21.6
25.2
28.8
32.4
36.0
43.2
43.2
50.4
Total power
kW
12.0
16.0
20.0
24.0
24.0
28.0
32.0
36.0
40.0
48.0
48.0
56.0
Evaporator
Type
Shell and Tube
Nominal water flow
m
3
/h
64
77
101
114
123
138
154
178
202
228
247
276
Water resistance
kPa
58
75
68
70
76
62
72
74
78
83
61
79
Maximum design
pressure (water side)
MPa
1.0
Victaulic connection
inch
4
5
6
8
Dimensions
Length
mm
3582
4482
5382
6282
6282
7182
8656
9556
10456
12259
12259
13159
Width
mm
2246
Height
mm
2367
2392
Weight
Shipping
kg
2880
3630
4560
4930
5050
5690
7220
8030
8820
9570
9800
11180
Operating
kg
2950
3740
4700
5100
5300
5940
7480
8340
9120
9950
10320
11690
Note:
Nominal cooling capacity is based on the following conditions: 12/7°C EWT and LWT, 35°C
ambient temperature;
Maximum running current refers to the maximum current when the unit is working in the
allowable area.
Shipping quality include steel packing quality. Operating quality include the quality of water in
the water-side heat exchanger, without steel packing quality.

Related product manuals