4 | P a g e
Installation
Unit installation
WARNING
Installation should be performed by experienced personnel. Avoid installing the equipment in a place
that could be dangerous during maintenance operations, such as (but not limited to) platforms without
parapets or railings, or areas not complying with the clearance requirements.
CAUTION
Installation must be performed in accordance with the installation instructions in
this Manual.
If the unit operates cooling mode when ambient temperature is lower than 5°C
and wind speed is more than 10 m/s, please consult manufacturer.
IMPORTANT
Install a strainer on the inlet to each heat exchanger. Failure to install a strainer
allows solid particles and/or welding slags to enter the heat exchanger. Installation
of a strainer with mesh size recommended by manufacturer (refer to page 16). The
manufacturer will not hold responsible for any damage to heat exchanger due to
blockage.
All other water piping outside the chiller must be protected against freezing.
Adjust the anti-vibration mountings beneath the equipment before connecting
water pipe.