5 | P a g e
Electrical installation
CAUTION
All electrical connections to the machine must be carried out in compliance with
laws and regulations in force.
All installation, operating and maintenance activities must be carried out by
qualified personnel.
Please refer to the specific wiring diagram for the machine that you have
purchased, and which was sent with the unit.
Should the wiring diagram not come with the machine, please contact your dealer
for further action.
Use copper conductors only. Failure to use copper conductors could cause
overheating or corrosion at the connection points and damages the unit.
To avoid interference, all control wires must be installed separately from the
power wires. Use separate electrical conduits for this purpose.
Before servicing the machine in any way, open the general disconnecting switch
on the machine's main power supply.
When the machine is off, but the disconnector switch is in the closed position,
unused circuits are live as well.
Never open the terminal board box of the compressors before having opened the
unit's general disconnecting switch.
In installations with power supply lines longer than 50 meters, inductive coupling
between phases and between phase and earth generates significant
electromagnetic field.
In order to limit these phenomena, it is good practice to lay out the phase wires
symmetrically, as described in the figure:
Chiller unit compressors are single-direction rotation compressors and can be damaged if
rotated in the wrong direction. For this reason, proper phasing of electrical power is
important. Terminal block indicator (R, S, T). R=L1, S=L2, T=L3