Water source modular chiller (heat pump)
Dimensions
UWL030B5 / UWL040B5
1800
1600
87
650
205 154
508
460
662
460
1400
650
614
Cable port
(
Installation hole)
(
Installation hole)
Unit
:
mm
Evaporator water inlet R2-1/2
Evaporator water outlet R2-1/2
Condenser water inlet R2-1/2
Condenser water outlet R2-1/2
Electrical
cabinet
Unit mm
Operating range
Performance Data
UWL030B5/UWL040B5
5 10 15 20 25 30
5
10
15
20
25
30
35
40
45
50
55
0
0
Area 1
Area 2
Area 3
EWT of condenser
℃
EWT of evaporator
℃
Notes:
1. During unit operating in area 1, the water
f low range should be 70%-130% of unit rated
water f low;
2. When EWT of evaporator lower than
10℃(area 2), unit may display anti-freezing
protection note (def ault 5℃). If need to
operate in this area, the water f low of the
evaporator shall meet the f ollowing
conditions:
UWL030B5≥30.5 m
3
/h
UWL040B5≥33.5 m
3
/h
3. When EWT of condensor higher than 45℃
(area 3 ), the water f low of the condenser
shall meet the f ollowing conditions:
UWL030B5≥23.5 m
3
/h
UWL040B5≥31.5 m
3
/h
4. Make sure water f low in using range. If
water flow is too low, it will reduce unit
perf ormance which caused by water scale,
or anti-freezing protection tripped, or
ref rigerant leakage which casued by rusting
and corrosion. If water flow is too large, it will
Notes:
1. During unit operating in area 1, the water ow
range should be 70%-130% of unit rated water
ow;
2. When EWT of evaporator lower than
10ºC (area 2), unit may display anti-freezing
protection note (default 5ºC). If need to operate
in this area, the water ow of the evaporator
shall meet the following conditions:
UWL030B5≥30.5 m
3
/h
UWL040B5≥33.5 m
3
/h
3. When EWT of condensor higher than 45ºC
(area 3 ), the water ow of the condenser shall
meet the following conditions:
UWL030B5≥23.5 m
3
/h
UWL040B5≥31.5 m
3
/h
4. Make sure water ow in using range. If water
ow is too low, it will reduce unit performance
which caused by water scale, or anti-freezing
protection tripped, or refrigerant leakage which
casued by rusting and corrosion. If water ow is
too large, it will cause shock corrosion.
EWT of condenser ºC
EWT of evaporator ºC
Area 1
Area 2
Area 3