Si71-502 Troubleshooting
Troubleshooting 53
1.18 Power Transformer
Error Detection
Method
Check resistance and voltage with tester, and insulation resistance with megger.
Error Generating
Conditions
Possible Causes
Troubleshooting
Resistance of primary side of transformer: approx. 140
Resistance of secondary side of transformer: approx. 1.9
Voltage at secondary side of transformer when rated voltage is applied to primary side: approx. 26 VAC
Insulation resistance between primary side of transformer and case: 100 M or higher
Insulation resistance between secondary side of transformer and case: 100 M or higher
Insulation resistance between primary side and secondary side of transformer: 100 M or higher
Check resistance of
primary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Check resistance of
secondary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Apply rated voltage to
primary side of
transformer, and check
output voltage of
secondary side
of transformer.
Does
measured
voltage deviate
significantly from
values shown
below?
YES
NO
Transformer is faulty.
Transformer is faulty.
Transformer is faulty.
Transformer is normal
(HF016)
(HL037)
Check resistance and voltage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VAM1500GJVE and is the answer not in the manual?

Daikin VAM1500GJVE Specifications

General IconGeneral
ModelVAM1500GJVE
TypeHeat Reclaim Ventilator
Air Flow1500 m³/h
Voltage220-240 V
Frequency50/60 Hz

Related product manuals