16 | Electrical installation
Installer and user reference guide
98
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
Note: When joining branch pipe ports, ONLY the combinations in above table are
possible. E.g.: it is NOT possible to join ports B and C.
Example When joining branch pipe ports A and B.
Examples
1. When connecting an indoor unit to branch pipe ports A, B,
and D, but NOT connecting an indoor unit to branch pipe
portC.
2. When joining branch pipe ports A and B. Connecting an
indoor unit to the joined branch pipe ports A and B, also to
branch pipe portC, but NOT connecting an indoor unit to
branch pipe portD.
ON
DS1 (A1P)
OFF
1 2 3 4
ON
DS2 (A1P)
OFF
1 2 3 4
16.5 To connect the external outputs
FAN output (extraction fan)
The extraction FAN output is a contact on terminal X6M that closes in case a leak is
detected, or when there is a failure or disconnection of the R32 sensor in the SV
unit.
The FAN output must be used when a ventilated enclosure is required (see
"13.3To determine the required safety measures"[445]).
a FAN output terminals (1 and 2)
b Cable to extraction fan circuit
Select and dimension the wiring in accordance with the applicable legislation based
on the information in the notice below:
NOTICE
The FAN output has a limited capacity of 220~240VAC – 0.5A.
Do NOT use the FAN output to directly power the fan. Instead, use the output to
energise a relay that controls the fan circuit.
a FAN output terminal
b Relay
c Extraction fan power supply