Servi ce
Manual
Heat Recovery 60 Hz
REYQ-AATJA/B, 208/230 V
REYQ-AAYDA/B, 460 V
SiUS372201EB

Table of Contents

Questions and Answers

  • Z
    zkeithAug 17, 2025
    What does it mean when my Daikin VRV EMERION REYQ192AAYDA shows error codes U4 or U5?
    • R
      Roger GibsonAug 17, 2025
      If your Daikin Heating System displays error codes U4 or U5, and restarts after a few minutes, it's likely due to communication interruption caused by electrical noises from other equipment. Try to identify and remove the sources of these electrical noises.
  • B
    bartonmichelleAug 20, 2025
    Why is COOL/HEAT selection disabled on my Daikin system?
    • P
      pvargasAug 20, 2025
      If COOL/HEAT selection is disabled on your Daikin Heating System, the remote controller may be displaying 'CENTRAL CONTROL'. If so, use a remote controller with the option to select cooling operation. If you have a COOL/HEAT selection remote controller, use it to select cool or heat.
  • S
    Sara JenkinsAug 23, 2025
    What does AA-03 error mean on my Daikin VRV EMERION REYQ192AAYDA Heating System?
    • M
      Madeline YoungAug 23, 2025
      To address the AA-03 error (Gas furnace abnormality) on the remote controller of your Daikin Heating System, try executing combustion heating operation once or reset the power source.
  • L
    lopezdennisAug 26, 2025
    Why is my Daikin VRV EMERION REYQ192AAYDA Heating System not cooling or heating air well?
    • B
      Brenda SmithAug 26, 2025
      If your Daikin Heating System isn't cooling or heating well, several factors could be the cause. Check for blocked air inlets or outlets on both the indoor and outdoor units and remove any obstructions. Ensure the air filters are clean. If the outdoor unit is enclosed, remove the enclosure. Verify that the set temperature and airflow rate are appropriately adjusted. Also, make sure windows and doors are tightly shut, and if cooling, use curtains or shades to block direct sunlight. The model must be selected to match the air conditioning load. If you're using the drying operation, switch to cooling for temperature reduction.
  • P
    Paul VasquezAug 28, 2025
    How to fix a Daikin VRV EMERION REYQ192AAYDA Heating System that does not start?
    • S
      Sarah LoganAug 28, 2025
      If your Daikin Heating System isn't starting, check the following: First, examine the fuses and replace any that have blown after turning off the power supply. Next, check the breakers; if any are in the OFF position, turn the power supply ON. If any breaker is tripped, leave the power supply OFF. Ensure there isn't a power failure; if there was, restart the system after the power is restored. Finally, turn off the power supply and verify that all connectors are securely plugged in.
  • A
    Alexander BanksAug 31, 2025
    What to do if Daikin VRV EMERION REYQ192AAYDA Heating System starts then stops immediately?
    • R
      rogershawAug 31, 2025
      If your Daikin Heating System starts and then stops immediately, it might be due to a blocked air inlet or outlet on either the indoor or outdoor unit; remove any obstacles. Another cause might be clogged air filters, so clean the air filters.
  • H
    henrygarrettSep 3, 2025
    Why does my Daikin Heating System emit odors?
    • R
      Rebecca FernandezSep 3, 2025
      If odors are coming from your Daikin Heating System during operation, the inside of the indoor unit should be cleaned.
  • N
    Natalie WilliamsSep 5, 2025
    Why is my Daikin VRV EMERION REYQ192AAYDA only doing fan operation?
    • J
      jessica03Sep 5, 2025
      If your Daikin Heating System is only operating the fan but not cooling or heating, the system may be in preparation mode. Wait for approximately 10 minutes.
  • P
    Phyllis NewtonSep 8, 2025
    Why doesn't my Daikin gas furnace start?
    • W
      webbjosephSep 8, 2025
      The gas furnace may not start if the compressor is operating, under stop-control, or immediately after defrost IN or defrost OUT. Wait until the operation becomes stable.
  • W
    williamsonrhondaSep 12, 2025
    Why does my Daikin VRV EMERION REYQ192AAYDA stop right after I turn it on?
    • K
      Kimberly ParksSep 12, 2025
      If your Daikin Heating System stops immediately after turning it on, the system might be in preparation mode. Wait approximately one minute.

Summary

Introduction

1. Safety Cautions

Essential safety precautions to prevent death or serious injury during repair and operation.

Part 1 General Information

5. Specifications

Provides detailed technical specifications for REYQ-AATJA, REYQ-AATJB, REYQ-AAYDA, and REYQ-AAYDB models.

Part 2 Refrigerant Circuit

1. Refrigerant Circuit (Piping Diagrams)

Illustrates the refrigerant piping diagrams for outdoor units, branch selector units, and indoor units.

2. Functional Parts Layout

Shows the physical layout and identification of functional parts within outdoor units.

3. Refrigerant Flow for Each Operation Mode

Details the refrigerant flow paths for cooling, heating, and simultaneous operations.

Part 3 Remote Controller

6. Service Settings Menu, Maintenance Menu

Outlines the menus and options available for service settings and maintenance procedures.

Part 4 Functions and Control

1. Operation Flowchart

Provides a visual flowchart illustrating the system's operation logic, including control modes.

7. Special Control

Covers special control functions such as pump down, oil return, defrost, and mode switching.

5. Basic Control

Explains the basic control mechanisms for compressors, fans, electronic expansion valves, and heat exchangers.

6. Protection Control

Details various protection controls like high pressure, low pressure, discharge pipe, and inverter protection.

Part 5 Field Settings and Test Operation

1. Field Settings for Indoor Unit

Details how to perform field settings for indoor units using the remote controller or other methods.

2. Field Setting from Outdoor Unit

Explains procedures for field setting directly from the outdoor unit PCB using DIP switches or PC configurator.

3. Field Settings for Branch Selector Unit

Provides instructions for setting field parameters for single and multi branch selector units.

4. Test Operation

Outlines the necessary checks and procedures for performing test operations on the installed system.

Part 6 Service Diagnosis

1. Symptom-based Troubleshooting

Guides on diagnosing and resolving issues based on observed system symptoms.

3.1 Error Codes and Descriptions

Lists all recognized error codes with their corresponding descriptions.

2. Error Code via Remote Controller

Explains how to check and interpret error codes displayed on the remote controller.

3.2 Error Codes (Sub Codes)

Details sub-codes associated with main error codes for more specific troubleshooting.

3. Troubleshooting by Error Code

Provides a comprehensive list of error codes, their descriptions, and troubleshooting steps.

3.4 External Protection Device Abnormality

Covers troubleshooting steps for errors related to external protection devices.

4.4 Power Transistor Check

Covers the procedure for checking power transistors on the PCB.

3.5 Indoor Unit Control PCB Abnormality

Provides troubleshooting guidance for abnormalities detected in the indoor unit control PCB.

3.33 Outdoor Unit Main;Sub PCB Abnormality

Details troubleshooting for abnormalities in the outdoor unit's main or sub PCB.

3.34 Detection of Ground Leakage by Leak Detection Circuit

Explains troubleshooting for ground leakage detection by the leak detection circuit.

3.7 Indoor Fan Motor Lock, Overload

Addresses troubleshooting for indoor fan motor lock or overload conditions.

4.7 Vacuuming and Dehydration Procedure

Explains the procedures for vacuuming and dehydrating the refrigerant system.

3.36 Activation of High Pressure Switch

Covers troubleshooting related to the activation of the high pressure switch.

3.37 Activation of Low Pressure Sensor

Details troubleshooting for the activation of the low pressure sensor.

3.38 Compressor Motor Lock

Provides troubleshooting steps when the compressor motor is locked.

4. Check

Outlines the necessary checks and procedures for diagnosing system issues.

3.39 Compressor Damage Alarm

Addresses troubleshooting for compressor damage alarms detected by the system.

3.52 High Pressure Sensor Abnormality

Guides on troubleshooting abnormalities in the high pressure sensor.

3.53 Low Pressure Sensor Abnormality

Covers troubleshooting for abnormalities in the low pressure sensor.

3.54 Inverter PCB Abnormality

Details troubleshooting for abnormalities detected in the inverter PCB.

3.57 Compressor Instantaneous Overcurrent

Details troubleshooting for compressor instantaneous overcurrent conditions.

3.58 Compressor Overcurrent

Addresses troubleshooting for compressor overcurrent conditions.

3.59 Compressor Startup Abnormality

Guides on troubleshooting abnormalities during compressor startup.

3.64 Refrigerant Shortage

Covers troubleshooting for refrigerant shortages.

Part 7 Appendix

1. Wiring Diagrams

Contains detailed wiring diagrams for outdoor units, branch selector units, indoor units, and air treatment equipment.

Daikin VRV EMERION REYQ192AAYDA Specifications

General IconGeneral
BrandDaikin
ModelVRV EMERION REYQ192AAYDA
CategoryHeating System
LanguageEnglish