14
7-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
Allowable length of transmission wirings and remote controller wiring are as follows.
(1) Outdoor unit - Indoor unit: Max. 1000m (Max. wiring length: 2000m)
(2) Indoor unit - Remote controller: Max. 500m
NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
CAUTION
• Arrange the wires and fix a cover firmly so that the cover does not float during wiring work.
• Do not clamp remote controller wiring and transmission wiring together with power supply wiring. Doing so
may cause malfunction.
• Remote controller wiring and transmission wiring should be located at least 50 mm from power supply wir-
ing. Not following this guideline may result in malfunction due to electrical noise.
8. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE
8-1 HOW TO CONNECT WIRINGS
Methods of wiring power supply, units and connecting remote controller wiring
• Power supply wiring and earth wire
Unscrew and remove the service cover.
Connect the power supply wiring and earth wiring to the power supply terminal block (3P).
When doing this, tie the power supply wiring and the earth wiring using the included clamp (small) (4) and
then firmly secure using the included clamp (small) (4) according to the figure.
(Refer to Fig. 23)
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Field
fuses
Wire Size Wire Size
FXAQ20ARVE6/FXARQ20ARVE6
FXAQ25ARVE6/FXARQ25ARVE6
FXAQ32ARVE6/FXARQ32ARVE6
FXAQ40ARVE6/FXARQ40ARVE6
FXAQ50ARVE6/FXARQ50ARVE6
FXAQ63ARVE6/FXARQ63ARVE6
H05VV - U3G
NOTE 1)
Wire size and
length must
comply with
local codes.
Vinyl cord with
sheath or cable
(2 wire)
NOTE 2)
0.75 - 1.25 mm
2
Model Hz Volts Voltage range MCA MFA kW FLA
15
15
15
15
15
15
15
15
15
15
15
15
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.048
0.2
0.3
0.3
0.3
0.4
0.6
0.2
0.3
0.3
0.3
0.4
0.6
FXAQ20ARVE6/FXARQ20ARVE6
FXAQ25ARVE6/FXARQ25ARVE6
FXAQ32ARVE6/FXARQ32ARVE6
FXAQ40ARVE6/FXARQ40ARVE6
FXAQ50ARVE6/FXARQ50ARVE6
FXAQ63ARVE6/FXARQ63ARVE6
FXAQ20ARVE6/FXARQ20ARVE6
FXAQ25ARVE6/FXARQ25ARVE6
FXAQ32ARVE6/FXARQ32ARVE6
FXAQ40ARVE6/FXARQ40ARVE6
FXAQ50ARVE6/FXARQ50ARVE6
FXAQ63ARVE6/FXAR
Q63ARVE6
Units
50
60
220-240
Max. 264
Min. 198
Max. 242
Min. 198
220
0.3
0.4
0.4
0.4
0.5
0.7
0.3
0.4
0.4
0.4
0.5
0.7
15A