EasyManua.ls Logo

Daikin VRV II Series - 2 Possible Outdoor Units Using R-410 A; Indoor Unit Capacity Index

Daikin VRV II Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
Systems • Introduction
3
• Introduction
2 Possible outdoor units using R-410A
2-1 Indoor unit capacity index
NOTE
1e.g. Selected indoor units: FXCQ25 + FXFQ100 + FXMQ200 + FXSQ40
Connection ratio: 25 + 100 + 200 + 40 = 365
Possible outdoor unit: RXYQ12M
VRV II heat pump Fixed combinations Nr. of outdoors Nr. of compressors Nr. of connectable indoor units Minimum capacity index Maximum capacity index
RXYQ5M RXYQ5M 1 1 8 63 163
RXYQ8M RXYQ8M 1 2 13 100 260
RXYQ10M RXYQ10M 1 2 16 125 325
RXYQ12M RXYQ12M 1 2 20 150 390
RXYQ14M RXYQ14M 1 3 20 175 455
RXYQ16M RXYQ16M 1 3 20 200 520
RXYQ18M RXYQ8M + RXYQ10M 2 4 20 225 585
RXYQ20M RXYQ10M x 2 2 4 20 250 650
RXYQ22M RXYQ10M + RXYQ12M 2 4 22 275 715
RXYQ24M RXYQ10M + RXYQ14M 2 5 32 300 780
RXYQ26M RXYQ10M + RXYQ16M 2 5 32 325 845
RXYQ28M RXYQ12M + RXYQ16M 2 5 32 350 910
RXYQ30M RXYQ14M + RXYQ16M 2 6 32 375 975
RXYQ32M RXYQ16M x 2 2 6 32 400 1,040
RXYQ34M RXYQ10M x 2 + RXYQ14M 3 7 34 425 1,105
RXYQ36M RXYQ10M x 2 + RXYQ16M 3 7 36 450 1,170
RXYQ38M RXYQ10M + RXYQ12M + RXYQ16M 3 7 38 475 1,235
RXYQ40M RXYQ10M + RXYQ14M + RXYQ16M 3 8 40 500 1,300
RXYQ42M RXYQ10M + RXYQ16M x 2 3 8 40 525 1,365
RXYQ44M RXYQ12M + RXYQ16M x 2 3 8 40 550 1,430
RXYQ46M RXYQ14M + RXYQ16M x 2 3 9 40 575 1,495
RXYQ48M RXYQ16M x 3 3 9 40 600 1,560
Model 20 25 32 40 50 63 80 100 125 200 250
Capacity index 20 25 31.25 40 50 62.5 80 100 125 200 250

Other manuals for Daikin VRV II Series

Related product manuals