VRV Systems Network Solution
20
5 Functions
5 - 2 Detailed Explanation of Functions
5 - 2 - 3 Display
(8) Interlocking Program Screen
Automatically starts and stops equipment that was set, in response to changes in the operating status of the facilities or the occurrence of errors. 8
types of input conditions can be specified.
Using this enables the interlocking of starting and stopping of a plurality of facilities (operation in order etc) indoor/outdoor link, key management link
and reporting.
1 link program can set a maximum of 50 input condition management items and a maximum of 50 start/stop output management items. A maximum
of 100 link programs can be defined. A plurality of link programs can be applied for input and output of the same management items.
The figure above is an example of a link program that is running air conditioners in common areas along
with the air conditioners that are running for certain tenants.
[Interlocking Program Screen]