VRV Systems Network Solution
34
7 Wiring Image
7 - 3 Wiring Specifications
No.
h
Wiring specification
• DIII-NET wiring
DAM602A51
DAM602B51
OPDI
Use sheathed vinyl cord (2-wire) or cable (0.75~2mm
2
)
Wire length: Max. 200m
(No polarity)
Control relay wiring
Wattmeter
Wattmeter
Key input
DAM602A51
DAM411A1
(option)
Polarity: No
Polarity: No
Polarity: No
Polarity: No
y
x
c
v
Fire alarm
input
Do-1 and Do-2 Settings
Ethernet communication wiring
DIII-NET wiring
Ethernet
10BASE-T
100BASE-TX
10BASE-T/100BASE-TX
straight cable
Field supplied
Outdoor
unit
Outdoor
unit
Outdoor
unit
Outdoor
unit
Recommended wire size 0.75~1.25mm²
Recommended wire size 0.75~1.25mm²
Terminal contact size: M3.5
DAM305B51,52
DAM602B51,52
Terminal contact size: M3.5
No voltage contact output specification is as follows
: Allowable current 10mA~1A
: Allowable voltage MW. AC250V
Lamp or the like
Lamp or the like
Recommended wire size 0.75~2mm²
Do-1
Do-2
Only as for DAM602B51
Terminal contact size: M3.5
Polarity: No
Polarity: No
Polarity: No
HUB
PC
NOTES
1 Up to four input devices can be connected to each G terminal. Do not connect three or more wires
togheter to one terminal.
2 Use micro-current contacts for no-voltage input contacts. (Voltage and current to be at DC 16 V and
below 10 mA with the contact closed)
3 The order of connections may flexibility be modified depending on the test-run settngs.
With a combination of OPDI, Di-2 and Di-3, total of 18 input devices can be connected.
CAUTIONS FOR WIRING
1 Do not use multicore cables with three or more cores
2 Use wires of sizes between 0.75mm
2
and 1.25mm
2
3 Do not bind the wire for DIII-NET
4 Wirings for DIII-NET must be isolated from the power lines
5 Wire length: Max 1000m
CAUTIONS FOR WIRING
1 Do not use multicore cables with three or more cores
2 Use wires of sizes between 0.75mm
2
and 1.25mm
2
3 Do not bind the wire for control
4 Wirings for control must be isolated from the power lines
5 Wire length: Max 150m