11 Troubleshooting
Installer and user reference guide
44
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03
Main code Cause Solution
The stop valve of an outdoor unit is left closed.
The piping and wiring of the specified indoor unit are not
connected correctly to the outdoor unit.
Open the stop valve on both the gas and liquid side.
Confirm that the piping and wiring of the specified indoor
unit are connected correctly to the outdoor unit.
In case of RXYSQ10+12:
Main code Sub code Cause Solution
Earth leakage detector activated Restart the unit. If problem reoccurs, contact your
dealer.
High pressure switch was activated (S1PH) - A1P
(X4A)
Check stop valve situation or abnormalities in
(field) piping or airflow over air cooled coil.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge unit.
Open stop valves
Stop valve closed (liquid) Open liquid stop valve.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge unit.
Open stop valves.
Low pressure malfunction:
Stop valve closed
Refrigerant shortage
Indoor unit malfunction
Open stop valves.
Check refrigerant amount+recharge unit.
Check the user interface's display or
transmission wiring between the outdoor unit
and the indoor unit.
Electronic expansion valve malfunction (subcool)
(Y2E) - A1P (X21A)
Check connection on PCB or actuator.
Electronic expansion valve malfunction (main)
(Y1E) - A1P (X23A)
Check connection on PCB or actuator.
Discharge temperature too high (R21T):
Stop valve closed
Refrigerant shortage
Open stop valves.
Check refrigerant amount+recharge unit.
Compressor casing temperature too high (R8T):
Stop valve closed
Refrigerant shortage
Open stop valves.
Check refrigerant amount+recharge unit.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge unit.
Open stop valves.
Ambient temperature sensor malfunction (R1T) -
A1P (X18A)
Check connection on PCB or actuator.
Discharge temperature sensor malfunction (R21T):
open circuit - A1P (X29A)
Check connection on PCB or actuator.
Discharge temperature sensor malfunction (R21T):
short circuit - A1P (X29A)
Check connection on PCB or actuator.
Compressor casing temperature sensor
malfunction (R8T): open circuit - A1P (X29A)
Check connection on PCB or actuator.
Compressor casing temperature sensor
malfunction (R8T): short circuit - A1P (X29A)
Check connection on PCB or actuator.
Suction temperature sensor malfunction (R3T) -
A1P (X30A)
Check connection on PCB or actuator.
De-icing temperature sensor malfunction (R7T) -
A1P (X30A)
Check connection on PCB or actuator
Liquid temperature sensor (after subcool HE)
malfunction (R5T) - A1P (X30A)
Check connection on PCB or actuator.
Liquid temperature sensor (coil) malfunction (R4T)
- A1P (X30A)
Check connection on PCB or actuator.
Gas temperature sensor (after subcool HE)
malfunction (R6T) - A1P (X30A)
Check connection on PCB or actuator.
High pressure sensor malfunction (S1NPH): open
circuit - A1P (X32A)
Check connection on PCB or actuator.
High pressure sensor malfunction (S1NPH): short
circuit - A1P (X32A)
Check connection on PCB or actuator.