19 Technical data
Installation and operation manual
37
RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452190-1D – 2020.10
After correcting the abnormality, press BS3 to reset the malfunction
code and retry operation.
The malfunction code which is displayed on the outdoor unit will
indicate a main malfunction code and a sub code. The sub code
indicates more detailed information about the malfunction code. The
malfunction code will be displayed intermittent.
Example:
Code Example
Main code
Sub code
With an interval of 1second, the display will switch between main
code and sub code.
19 Technical data
A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
19.1 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and
the minimum space for ventilation is available (refer to the figure
below).
(mm)
≥500
≥500
≥900
≥900
≥20
≥20 ≥20
≥20 ≥20
≥20
F
(mm)
≥300
F Front side
INFORMATION
Further specifications can be found in the technical
engineering data.
19.2 Piping diagram: Outdoor unit
A
C
D
BBB
SV
SV
SV
M
SV
SV
HPS
SV
SV
SENPH
SENPL
4D108945A
A Charge port
B Stop valve (with service port 7.9mm flare
connection)
C Cooling water inlet
D Cooling water outlet
Charge port / Service port
Filter
Check valve
Pressure relief valve
Solenoid valve
Capillary tube
Electronic expansion valve
4‑way valve
Propeller fan
Port (for sensor)
Low/high pressure sensor
High pressure switch
Oil separator
Accumulator