Questions and Answers

  • L
    lwattsSep 8, 2025
    What does warning indication mean on Daikin Air Conditioner about leak detection?
    • J
      Joan BowenSep 9, 2025
      If your Daikin Air Conditioner is showing a warning indication that leak detection or refrigerant amount check was not performed, execute the autocharge function. Note that the unit may not be ready for leak detection functionality.
  • A
    angela26Aug 23, 2025
    Why is my Daikin VRV IV+ RXYTQ8U7YF not turning on?
    • J
      Jared Ramos DDSAug 23, 2025
      If your Daikin Heat Pump system doesn't operate at all, first check for any power failures and wait for the power to be restored. If a power failure occurred during operation, the system should automatically restart immediately after power is restored. Next, check if any fuses have blown or breakers have been activated. Replace the fuse or reset the breaker if needed.
  • G
    Gloria BlanchardAug 25, 2025
    What to do if my Daikin Heat Pump shows a malfunction code?
    • A
      Ana MartinAug 25, 2025
      If the user interface display of your Daikin Heat Pump indicates the unit number, the operation lamp flashes, and a malfunction code appears, notify your installer and report the malfunction code.
  • P
    Peter JonesAug 26, 2025
    What to do if my Daikin VRV IV+ RXYTQ8U7YF Heat Pump is leaking water?
    • J
      Jason VangAug 27, 2025
      If water is leaking from your Daikin Heat Pump unit, stop the operation.
  • J
    James MorganAug 27, 2025
    What to do if my Daikin VRV IV+ RXYTQ8U7YF only runs in fan mode?
    • D
      Daniel EvansAug 27, 2025
      If your Daikin Heat Pump system only operates in fan mode and stops when switching to heating or cooling, check if the air inlet or outlet of the outdoor or indoor unit is blocked by obstacles. Remove any obstructions to ensure free airflow. Also, check if the user interface displays a message indicating it's time to clean the air filter.
  • L
    Lauren LeonardSep 22, 2025
    What to do for timeout on autocharge procedure on Daikin Air Conditioner?
    • B
      Bryan LiSep 22, 2025
      If your Daikin Air Conditioner displays a timeout on the autocharge procedure, immediately close valve A and push BS1 to reset. Check if the gas side stop valve is opened correctly, if the valve of the refrigerant cylinder is opened, and if the air inlet and outlet of the indoor unit are not obstructed.
  • H
    Heather CastilloSep 16, 2025
    How to fix ambient temperature sensor malfunction on Daikin Air Conditioner?
    • J
      Jasmine CarsonSep 16, 2025
      If your Daikin Air Conditioner is showing an ambient temperature sensor malfunction, check the connection on the PCB or actuator.
  • E
    Erica WebsterSep 18, 2025
    How to fix earth leakage detector malfunction on Daikin Air Conditioner?
    • R
      Richard SchneiderSep 18, 2025
      If your Daikin Air Conditioner shows an earth leakage detector malfunction due to an open circuit, check the connection on the PCB or actuator.
  • P
    Paula TerrySep 7, 2025
    How to correct reversed power supply phase malfunction in Daikin Air Conditioner?
    • D
      Dawn RamirezSep 7, 2025
      If your Daikin Air Conditioner shows a reversed power supply phase malfunction, correct the phase order.
  • M
    Michael HaynesSep 4, 2025
    How to fix Daikin Air Conditioner when earth leakage detector activated?
    • J
      James CookSep 4, 2025
      If the earth leakage detector is activated on your Daikin Air Conditioner, restart the unit. If the problem continues, contact your dealer.

Daikin VRV IV+ RXYTQ8U7YF Specifications

General IconGeneral
ModelRXYTQ8U7YF
TypeHeat Pump
Cooling Capacity (kW)22.4
Heating Capacity (kW)25.0
RefrigerantR410A
Power Supply380-415V, 3Ph, 50Hz
Operating Temperature (Cooling)-5 to 46 °C