EasyManua.ls Logo

Daikin VRV Series - Field Settings

Daikin VRV Series
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
3P184443-12N English
11. FIELD SETTINGS
CAUTION
Whenperformingeldsettingortestrunwithoutattachingthedecorationpanel,donottouch
the drain pump. This may cause electric shock.
Check that the outdoor unit has been wired properly.
(1) Make sure the control box cover is closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation
conditions.
Settings can be made by changing the “MODE NO.”, “FIRST CODE NO. and “SECOND CODE
NO.”.
The “Field Settings” included with the remote control lists the order of the settings and method of
operation.
Setting is made in all units in a group. To set for individual indoor units or to check the setting, use
the mode No. (with “2” in upper digit) in parentheses ( ).
Mode
10
Field settings
0
01
4
–––
8
–––
Return Setting
FIELD SET MODE
MODE NO.
SECOND CODE NO.FIRST CODE NO.
Fig. 32
11-1 SETTING AIR OUTLET DIRECTION
See the installation manual included with the sealing material of air discharge outlet kit, sold separately
and technical guide, for ceiling height settings for two and three-direction air discharge.
(The SECOND CODE NO. is factory set to “01” (all round outlet) before shipping.)
11-2 SETTING FOR OPTIONS
For settings for options, see the installation manual provided with the option.
11-3 SETTING AIR FILTER SIGN
Remote controllers are equipped with liquid crystal display air lter signs to display the time to clean air
lters.
Change the SECOND CODE NO. according to Table4 depending on the amount of dirt or dust in the
room.
SECOND CODE NO. is factory set to “01” for air lter contamination-light.
Table 4
Setting
Spacing time of display air
lter sign (long life type)
MODE NO.
FIRST
CODE NO.
SECOND
CODE NO.
Air lter contamination : light Approx. 2500 hrs
10 (20) 0
01
Air lter contamination : heavy Approx. 1250 hrs 02

Other manuals for Daikin VRV Series

Related product manuals