IOM 1322 • WATER-COOLED SCROLL COMPRESSOR 34 www.DaikinApplied.com
It is recommended that isolators be used on all upper level
installations or in areas where vibration transmission is a
consideration.
Figure 28: Isolator Locations
Table 15: Isolator Kit Part Numbers
WGZ-DW Packaged Chiller Isolator Kit Part Numbers
Model Number 030-060 070-080 90 100-130 150-200
332320501 332320502 332320503 332320504 332320505
R -I-S 332325501 332325502 332325502 332325503 332325503
WGZ-DA Remote Condenser Isolator Kit Part Numbers
Model Number 030-060 070-080 090-115 130 150-200
332320506 332320507 332320508 332320509 332320510
R-I-S 332325504 332325501 332325501 332325501 332325505
Table 16: Vibration Isolator Mounting Locations (Packaged
Chillers)
Transfer the unit as indicated under Moving the Unit.“ In
all cases, set the unit in place and level. When spring-type
isolators are required, install springs running under the main
unit supports.
The unit should be set initially on shims or blocks at the listed
spring free height. When all piping, wiring, ushing, charging,
etc., is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed.
A rubber anti-skid pad should be used under isolators if
holddown bolts are not used.
Installation of spring isolators requires exible piping
connections and at least three feet of exible electrical conduit
to avoid straining piping and transmitting vibration and noise.
Refer to unit dimension drawing for mounting locations.