IOM 1322 • WATER-COOLED SCROLL COMPRESSOR 56 www.DaikinApplied.com

Alarm description (as shown on screen):
Phase/Voltage Cir N
Trigger: PVM input is low and Phase Voltage set point =
enable.
Action Taken: Rapid stop circuit
Reset: Auto reset when PVM input is high

Alarm description (as shown on screen): Ground Fault Cir N
Trigger: GFP input is low and Ground Fault set point = enable.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad.

Alarm description (as shown on screen):
Low OAT Start Fail N
Trigger: Circuit has failed three low OAT start attempts
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad.
In order to avoid low evaporator pressure alarms at startup
view “Low Ambient Start (WaterCooled = NO)” on page 68

Alarm description (as shown on screen):
Evap Water Freeze
Trigger: Evaporator LWT drops below evaporator freeze
protect set point AND Unit State = Auto
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad
or via the BAS clear alarm signal, but only if the alarm trigger
conditions no longer exist.
Leaving Evaporator Water Temperature

Alarm description (as shown on screen):
Evap LWT Sens Fault
Trigger: Sensor shorted or open
Action Taken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.
Leaving Condenser Water Temperature

Alarm description (as shown on screen):
CondLWT Sens Fault
Trigger: Sensor shorted or open AND TGZ unit (refrig =
R134a) AND operating in ‘heat’ mode.
Action Taken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.

Alarm description (as shown on screen):
SuctT Sensor Fail N
Trigger: Sensor shorted or open AND Expansion Valve Type =
Electronic
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.

Alarm description (as shown on screen):
EvapP Sensor Fail N
Trigger: Sensor shorted or open. If failing high (open),
logic has been added that requires the Leaving Evaporator
Temperature to be below 75°F. This will prevent nuisance trips
due to conditions where the evaporator water temperature is
high which could cause false alarms.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.

Alarm description (as shown on screen):
CondP Sensor Fail N
Trigger: Sensor shorted or open
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.
Condenser Entering or Outdoor Air

Alarm description (as shown on screen): OAT Sensor Fault
Trigger: Sensor shorted or open
Action Taken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range

Alarm description (as shown on screen):
Evap Water Freeze
Trigger: Evaporator LWT drops below evaporator freeze
protect set point AND Unit State = Auto
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad
or via the BAS clear alarm signal, but only if the alarm trigger
conditions no longer exist.
