Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu
.
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for Graphical LCP (GLCP)
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s
4. The frequency converter is now programmed according to
default settings
This parameter initialises all except:
Par. 15-00
Operating Hours
Par. 15-03
Power Up's
Par. 15-04
Over Temp's
Par. 15-05
Over Volt's
5 How to Operate the Frequency Converter ADAP-KOOL
®
Drive AKD 102 High Power
64