6 – Appendix UK
2.1.3 Additional label:
Weight when full (kg)
DHP-H 4
405
DHP-H 6
409
DHP-H 8
409
DHP-H 10
409
DHP-H 12
418
DHP-H 16
422
DHP-A 6
440
DHP-A 8
440
DHP-A 10
440
DHP-A 12
448
Heat Pump *)
*) Incl. DHP Opti and Opti Pro
This label will ensure that this product conforms to the
requirements of United Kingdom Building Regulations.
The information is entirely valid in a UK specific installations.
Maximum water supply pressure 10 bar
Pressure reducing valve 3 bar
Expansion valve 6 bar
Expansion vessel charge pressure 3 bar
Operating pressure 5,5 bar
Temp and pressure release valve 10 bar; 90−95˚C
Maximum primary working pressure 1,5 bar
Immersion heater D76 / 9 kW / 230 V
WARNING TO THE USER
(a) Do not remove or adjust any component part of this
unvented water heater. Contact the installer.
(b)
If this unvented water heater develops a fault, such
as a flow of hot water from the discharge pipe,
switch the heater off and contact the installer.
WARNING TO THE INSTALLER
(a) This installation is subject to building regulation
approval,
notify the Local Authority of intention to
install.
(b)
Use only manufacturer's recommended
replacement parts.
(c) INSTALLED BY:
Name._____ _ _____ _ _____ _____ _ _____ _ _____ _____ _ _
Address.______ _ _____ _ ____ _ _____ _ _____ _____ _ ____
Tel No.____ _ _____ _ _____ _____ _ _____ _ _____ _____ _ __
Completion date._ _ ____ _ _____ _ _____ _ ____ _ _____ _ __