Parameter Meaning
POOL CIRCUIT Used to indicate where the reversing valve for pool is located.
The system supply circuit cannot be used if external auxiliary heater is configured.
Factory setting: SYSTEM SUPPLY, range: SYSTEM SUPPLY - DISTRIBUTION CIRCUIT 1
- DISTRIBUTION CIRCUIT 2
MAX TIME POOL determines the longest permitted pool heating time at non-inte-
gral controlled circuit.
Factory setting: 40M, range 1M – 210M
MAX TANK TEMP Maximum permitted temperature in the buffer tank. Fixed value 55°C is used if no
external auxiliary heater is configured. At external auxiliary heater the temperature
can be set between 55°C – 80°C.
Factory setting: 55°C, range: 55°C – 80°C
64 – Installation instructions VMGFD102