12 Technical data
Table 4. Technical data
DHP-AQ 6 9 11 13 16 18
Type Air/water
Refrigerant Type R407C
Amount kg 4,0 4,3 5,0 5,1 5,7 6,0
Test pressurisation MPa 3,4
Design pressure MPa 3,1
Compressor Type Scroll
Oil POE
Electrical data 3-N 50Hz
heat pump
Mains power supply V 400
Rated output, com-
pressor
kW 2,2 2,9 3,3 4,2 5 6,1
Rated output, fan kW 0,18 0,28 0,72
Start current
10
A 12 10 18 17 18
Fuse A 10 16
Electrical data 3-N, 50Hz
control unit
Mains power supply V 230/400
Rated output, circ.
pump
8
kW 0,07 0,14
Auxiliary heater, 5
step
8
kW 3/6/9/12/15
Fuse A
10
12
/16
13
/16
14
/20
15
/25
16
Electrical data 1-N 50Hz
heat pump
Mains power supply V 230
Rated output, com-
pressor
kW 2,4 2,8 3,6 4,3 5,5 -
Rated output, fan kW 0,18 0,28 -
Start current
10
A 11 21 26 28 -
Fuse A 20 20 32 32 32 -
Electrical data 1-N, 50Hz
control unit
Mains power supply V 230
Rated output, circ.
pump
8
kW 0,07 0,14
Auxiliary heater, 3
step
8
kW 3/6/9
Fuse A
16
17
/30
18
/40
19
Performance
11
COP
1
3,26 3,40 3,44 3,38 3,21 3,10
Heat factor
1
kW 4,73 6,22 7,68 9,10 11,40 13,26
Incoming power
1
kW 1,45 1,83 2,23 2,69 3,56 4,28
COP
2
4,32 4,38 4,54 4,35 4,12 3,97
Heat factor
2
kW 6,49 8,59 10,64 12,30 15,21 17,59
Incoming power
2
kW 1,50 1,96 2,34 2,83 3,69 4,42
COP
3
4,73 4,73 5,01 4,67 4,61 4,25
Heat factor
3
kW 6,87 8,81 10,91 12,64 15,88 18,58
Incoming power
3
kW 1,45 1,86 2,18 2,70 3,44 4,37
EER
4
2,23 2,35 2,55 2,41 2,29 2,33
Cooling output
4
kW 4,21 5,85 7,52 8,85 10,39 13,16
Installation instructions VMGFD102 – 71