EasyManuals Logo
Home>Danfoss>Controller>EKC 315A

Danfoss EKC 315A User Manual

Danfoss EKC 315A
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
EKC 315A Manual RS8CS302 © Danfoss 07-2005 9
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage
The controller can give the following messages:
E1
Error message
Fault in controller
E11 Valve’s actuator temperature outside its range
E15 Cut-out S2 sensor
E16 Shortcircuited S2 sensor
E17 Cut-out S3 sensor
E18 Shortcircuited S3 sensor
E19
The input signal on terminals 18-19 is outside
the range.
E20
The input signal on terminals 14-15 is outside
the range (P0 signal)
A1
Alarm message
High-temperature alarm
A2 Low-temperature alarm
A11 No refrigerant has been selected
Define input signal on the analoge input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3: Displacement of superheat reference. 0-20 mA
4: Displacement of superheat reference. 4-20 mA
o10 0 4 0
Set supply voltage frequency
o12 50 Hz 60 Hz 0
Select display for ”normal picture”
1: Superheat
2: Valve’s opening degree
3: Air temperature
o17 1 3 1
Manual control of outputs:
OFF: no manual control
1: Relay for solenoid valve: select ON
2: AKV/A output: select ON
3: Alarm relay activated (cut out)
o18 off 3 Off
Working range for pressure transmitter – min.
value
o20 -1 bar 60 bar -1.0
Working range for pressure transmitter – max.
value
o21 -1 bar 60 bar 12
(Setting for the function o09)
Set the temperature value or opening degree
where the output signal must be minimum (0 or
4 mA)
o27 -70°C 160°C -35
(Setting for the function o09)
Set the temperature value or opening degree
where the output signal must be maximum (20
mA)
o28 -70°C 160°C 15
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503.
11=R114. 12=R142b. 13=User defined. 14=R32.
15=R227. 16=R401A. 17=R507. 18=R402A.
19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270.
o30 0 29 0
Service
TQ valve's actuator temperature
u04 °C
Reference of the valve's actuator temperature
u05 °C
Analog input AIA (18-19) u06 mA
Analog output AO (2-5)
u08 mA
Read status of input DI
u10 on/off
Thermostat cut-in time
u18 min.
Temperature at S2 sensor
u20 °C
Superheat
u21 K
Superheat reference
u22 K
Read AKV valve’s opening degree
u24 %
Read evaporating pressure
u25 bar
Read evaporating temperature
u26 °C
Temperature at S3 sensor
u27 °C
Temperature reference
u28 °C
Read signal at pressure transmitter input
u29 mA
*) This setting will only be possible if a data communication module has been
installed in the controller.

Other manuals for Danfoss EKC 315A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 315A and is the answer not in the manual?

Danfoss EKC 315A Specifications

General IconGeneral
BrandDanfoss
ModelEKC 315A
CategoryController
LanguageEnglish

Related product manuals