EasyManua.ls Logo

Danfoss EKC 326A - Receiver Control and Actuator Settings; Heat Recovery and Receiver Control; Actuator Type and ETS;CCM Configuration

Danfoss EKC 326A
12 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
 EKC 326A  Instructions  RI8NG552  ©  Danfoss  10/2011  7
*) This setting will only be possible if a data communication module has been installed in the 
controller.
**) The display on the controller can show 3 digits only, but  the setting value has 4 digits. Only the 
3 most important will be shown. It means fx. 250 will give a setting of 2500.
Miscellaneous
Digital input signal - DI 
0: The input is not used
1: External main switch
2: additional cooling capacity
o02 0 2 0
Controller’s address o03* 0 240 -
ON/OFF switch (service-pin message) o04* - - -
Set supply voltage frequency o12
50Hz 
(0)
60 Hz 
(1)
0
Pressure transmitter range Pgc - min. o20 -1 bar 5 bar -1
Pressure transmitter range Pgc - max. o21 6 bar 199 bar 159
Pressure transmitter range Prec - min. o47 -1 bar 5 bar -1
Pressure transmitter range Prec - max. o48 6 bar 199 bar 59
Service
Signal on AI the input u07 V
Read status of input DI u10 on/off
Read ETS/CCM valves opening degree u24 %
Calculated reference for regulation (desired pres-
sure in the gas cooler)
U03 bar
The output signal to the ICMTS valve converted 
into opening degree
U04 %
The temperature in the gas cooler. Measured 
using temperature sensor Sgc.
U05 °C
The pressure in the gas cooler. Measured using 
pressure transmitter Pgc.
U06 bar
The pressure in the receiver. Measured using 
pressure transmitter Prec, but only if it is 
mounted.
U07 bar

Other manuals for Danfoss EKC 326A

Related product manuals