EKC 347  Manual  RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020  ©  Danfoss  01-2011  5
Configuration of limit alarm (A3) level and lower limit alarm(A2) for pump cut-
out.
To dene whether the limit alarm (A3) is linked to rising (A18=0) or falling level 
(A18=1).
 It is also possible to congurate the Relay for lower level limit when lower limit alarm 
(A2) is detected. Dedicated to switch o pumps at low level alarm. 
0:  Rising level. When liquid level is higher than A16, and time in A17 has expired,  A3 
alarm is generated. 
1: Falling level . When liquid level is lower than A16, and time in A17 has expired, A3 
alarm is generated.
2: Same function as if A18=0, but in addition (to that:
- When liquid level is higher than A02. No A2 alarm and Relay for lower level limit,  
gives ON signal (cut in) on terminal 8 and 10.
- When liquid level is lower than A02 and time in A15 has expired. A2 alarm is gener-
ated and Relay for lower level limit,  gives OFF signal (cut out) on terminal 8 and 10.
3: Same function as if A18=1, but in addition (to that:
- When liquid level is higher than A02. No A2 alarm and Relay for lower level limit,  
gives ON signal (cut in) on terminal 8 and 10.
- When liquid level is lower than A02 and time in A15 has expired. A2 alarm is gener-
ated and Relay for lower level limit,  gives OFF signal (cut out) on terminal 8 and 10.
A18 A18 Lim. LowMode
Function Alarm relay when A1, A2 or A3 alarms are detected.
0: Alarm relay to be activated when A1 or A2 or A3 are detected.
1: Alarm relay only to be activated when A3 is detected.
A19 A19 Alarm type 
(With setting = 0 the alarm is also 
transmitted via the data communica-
tion)
Alarm relay
The alarm relay will become activated if one of the set limits is exceeded or if the 
controller loses the input signal from the level-measuring unit.
With data communication the impor-
tance of the individual alarms can be 
dened. Setting is carried out in the 
“Alarm destinations” menu. See also 
page  11.
Control parameters Injection Settings
Definition of regulating principle
Here you set whether the controller is to open or close the valve when the liquid level 
is rising.
Low (0):  Regulation on the low-pressure side. The valve closes when liquid level is 
rising.
High (1):  Regulation on the high-pressure side. The valve opens when liquid level is 
rising.
n35 n35 Low/High Pr.
Period time
An AKV/A valve is operated with pulses of a given length. The length depends on the 
opening degree required. If a large opening degree is required, the pulse will last for 
an entire period time. A period time will thus comprise both open and closed valve.
n13 n13 AKV per.time
P - band
If the value is reduced the regulating range will be reduced. (The P-band will be near 
the reference).
n04 n04 P-band
I: Integration time Tn
The I-link can be made passive by setting the value at max. (600s)
(If the Tn value is increased the regulation becomes slower).
n05 n05 Tn sec.
Neutralzone
The function is only active if the selected expansion valve is of type ICM
n34 n34 Neutralzone
Min. opening degree
Here you can make a setting if you require a limitation of the valve’s working range.
n33 n33 OD Min.
Max. opening degree
Here you can make a setting if you require a limitation of the valve’s working range.
n32 n32 OD Max.