  • C
    claytongarciaJul 28, 2025
    Why is the Danfoss ICM Control Unit valve position feedback signal not working with my controller/PLC?
    • J
      johnstewartJul 28, 2025
      Several factors could be at play. First, ensure no external power supply is interfering with the 4-20mA/0-20mA feedback loop; remove any such power source. Second, a wiring issue might exist. Check service parameter ¡53 to see the ICAD output, and if needed, use an ammeter to check the current output via the yellow and blue wires in the ICAD control cable. Finally, verify that the feedback output signal hasn't been disabled in parameter ¡06 and correct the setting if necessary.
  • D
    David RyanAug 7, 2025
    What to do if the Danfoss ICM Control Unit valve does not appear to be opening or closing properly?
    • A
      alexandervasquezAug 7, 2025
      First, check that the ICAD is mounted evenly on the ICM valve. Second, use the service parameters (¡51 for a mA input or ¡52 for a voltage input) to check the input signal that the ICAD is receiving.
  • H
    hollywashingtonAug 18, 2025
    How to fix Danfoss ICM when A1 is flashing and valve is not working?
    • C
      ccookAug 18, 2025
      The ICM valve size was not selected in parameter ¡26. Refer to the programming section on page 9.

Summary

Introduction

ICM;ICAD Overview

Overview of ICM/ICMTS motorized valves and CVE pressure regulating pilot.

Installation

Mechanical Installation

Instructions for installing ICM and ICMTS valves and ICAD motor actuators.

Electrical Data and Wiring

Details on supply voltage, data communication, and wiring connections for ICAD.

ICAD Actuator Configuration

Control and Operation Parameters

Parameters for defining ICAD operating mode, input signals, and control functions.

Advanced and System Parameters

Parameters for alarm configuration, boost functions, system settings, and display.

Network and Communication Parameters

Parameters for Modbus communication, baud rate, and parity settings.

Status, Alarms, and Troubleshooting

Status and I;O Monitoring

Readout of digital I/O states, next service information, and supply status.

Alarm and Event Log Parameters

Detailed alarm timestamps, event log entries, and active alarm/warning indicators.

Troubleshooting Tips and FAQs

Guidance for diagnosing and resolving common operational issues and answers to FAQs.

Info and Online Support

ICAD Information and Parameters

Details on ICAD name, model, versions, serial number, and non-displayed parameters.

Online Support Resources

Access to product store, technical documentation, learning, and spare parts.

Danfoss ICM Specifications

General IconGeneral
Input Voltage24 V AC/DC
ApplicationHVAC
TypeElectronic controller
MediaAir, water
Operating Temperature0°C to +50°C
Communication ProtocolModbus

Related product manuals